: Without a 120 Ω resistor at both ends of the main line, signals can reflect and distort, causing the receiver to miss bytes.
Disconnect the slave device and short the TX+ and RX- pins on your RS485 converter. Send a Modbus request. If you receive an echo, your serial port and cable are fine. If not, the issue is hardware-related. modbus poll bytes missing error fixed
Even though RS-485 is differential, a floating ground can cause enough noise to drop bytes. Ensure a signal ground wire connects all devices. 2. Adjust Timing and Timeouts : Without a 120 Ω resistor at both
Cheap, non-isolated adapters often struggle with high baud rates. If you’re seeing missing bytes consistently, try lowering your baud rate to 9600 to see if stability improves. 2. Adjust Modbus Poll Timeout Settings If you receive an echo, your serial port and cable are fine
Here is a step-by-step guide to identifying the root cause and fixing it.
How to Fix "Modbus Poll Bytes Missing" Errors: A Troubleshooting Guide